Pietro FiorentiniAperflux 851
Gas Pressure Regulators
价格面议

Axial Flow, True Fail Open
ASX 176/FO is the Fail Open version of Pietro Fiorentini's axial-flow ASX 176 family: a balanced, pilot-operated plug-and-seat regulator for high-pressure transmission and medium-pressure distribution. DN 25 to DN 150, inlet 3 to 100 barg, outlet 1 to 74 barg, Cg up to 19000.





本节目前仅提供英文版本

Gas transmission stations where supply continuity matters…

Power-generation fuel-gas supply and gas-reverse-flow…

LNG marine transportation and gas liquefaction

Heavy industry with high gas demand
本节目前仅提供英文版本
ASX 176/FO is the Fail Open version of Pietro Fiorentini's axial-flow ASX 176 family: a balanced, pilot-operated plug-and-seat regulator for high-pressure transmission and medium-pressure distribution. DN 25 to DN 150, inlet 3 to 100 barg, outlet 1 to 74 barg, Cg up to 19000.
The ASX 176/FO takes the axial body of the ASX 176 and turns it into a regulator that, by the manufacturer's description, is a true Fail Open plug-and-seat design. Under EN 334 a Fail Open regulator moves toward open if the control loop fails, which is the required behaviour where the downstream supply must not be interrupted by a regulator fault, for example when the regulator sits in series with a monitor or slam-shut that provides the overpressure protection.
The FO version has a different working window: inlet pressure starts at 3 barg (the Fail Close ASX 176 starts at 0.8 barg), outlet pressure ranges from 1 to 74 barg, and the minimum operating differential pressure is 2 barg. Accuracy class is up to 2.5 and lock-up class up to 10, against 1 and 5 for the ASX 176. The three main pilots are 204/A/FO (1 to 33 barg), 205/A/FO (20 to 60 barg) and 207/A/FO (41 to 74 barg). As in the rest of the family, set-point adjustment is made by a pilot that controls the pressure on the motorization diaphragm chamber, the regulator is balanced, and the axial body keeps it reliable with elemental sulphur in the gas.
The same sizing coefficients as the ASX 176 apply (Cg 630, 2300, 5000, 8800 and 19000 for DN 25 to DN 150, K1 = 145), and the standard weights are identical: 55, 72, 123, 214 and 333 kg in Class 300.
ASX 176/FO is supplied by Barmaan to order: send us the gas, the inlet pressure range, the required outlet set point, the maximum flow and the line size and flange class, and we quote the matching configuration, pilot range and accessories. Price, availability and lead time are confirmed in the quotation; this page does not publish a price. Barmaan is not presented here as a manufacturer; all technical data on this page is taken from the manufacturer's published flyer and technical brochure, which are attached below. Conformity documents for a specific project can be requested through the quotation.
| 参数项 | 参数值 |
|---|---|
| General | |
| Manufacturer | Pietro Fiorentini S.p.A. — Arcugnano (Vicenza), Italy |
| Type | Pilot-operated, balanced gas pressure regulator (high-medium pressure) |
| Fail action (EN 334) | Fail Open (true plug-and-seat) |
| Suitable media | Previously filtered, non-corrosive gases (natural gas; biomethane; NG-H2 blends) |
| Pressure and performance | |
| Design pressure (PS) | up to 10.2 MPa | 102 barg |
| Inlet pressure (MAOP) | 0.3 to 10 MPa | 3 to 100 barg |
| Downstream (outlet) pressure range Wd | 0.1 to 7.4 MPa | 1 to 74 barg |
| Minimum operating differential pressure | 0.2 MPa | 2 barg |
| Accuracy class (AC) | up to 2.5 |
| Lock-up pressure class (SG) | up to 10 |
| Ambient temperature (TS) | -20 °C to +60 °C |
| Inlet gas temperature | -20 °C to +60 °C |
| Flow coefficient Cg by size (DN) | DN 25: 630; DN 50: 2300; DN 80: 5000; DN 100: 8800; DN 150: 19000 |
| Form factor K1 | 145 |
| Main pilot models and setting ranges | 204/A/FO: 1 to 33 barg; 205/A/FO: 20 to 60 barg; 207/A/FO: 41 to 74 barg |
| Pilot setting options | /A manual; /D electric remote; /CS pneumatic remote; /FIO smart unit (remote setting, monitoring, flow limitation) |
| Construction and sizes | |
| Nominal sizes | DN 25 | 1 in; DN 50 | 2 in; DN 80 | 3 in; DN 100 | 4 in; DN 150 | 6 in |
| End connections | ASME B16.5 Class 300 and 600, RF or RTJ |
| Body | Steel ASTM A350 LF2; plug ASTM A350 LF2 nickel-coated on the sealing surface |
| Seat | Polymer / nitrile rubber vulcanized on a metal support |
| Diaphragm | Rubberized canvas (hot-pressed); sealing ring: nitrile rubber |
| Available accessories | LDB/176 silencer; PM/176 monitor; SSX/176 slam-shut |
| Weight (standard version, by size) | ANSI 300: 55 / 72 / 123 / 214 / 333 kg; ANSI 600: 55 / 74 / 126 / 225 / 365 kg (DN 25 / 50 / 80 / 100 / 150) |
| Face-to-face length (by size) | ANSI 300: 197 / 267 / 317 / 368 / 473 mm |
| Standards and compliance | |
| Design standard and approval | Designed to EN 334; certified to Directive 2014/68/EU (PED), CE |
| Leakage class | Bubble-tight, better than Class VIII to ANSI/FCI 70-3 |
| Hydrogen / biomethane | Hydrogen Ready for NG-H2 blending; biomethane compatible; 20% hydrogen blending compatible, higher blending available on request |
同系列的其他型号 — 仅供参考,非库存产品。
本节目前仅提供英文版本
| 型号代码 | 说明 | 测量范围 |
|---|---|---|
| 204/A/FO | Main pilot 204/A/FOManual-setting main pilot for the Fail Open version; /D, /CS and /FIO remote-setting versions are listed by the manufacturer. | 0.1 - 3.3 MPa (1 - 33 barg) |
| 205/A/FO | Main pilot 205/A/FOManual-setting main pilot for the Fail Open version; /D, /CS and /FIO remote-setting versions are listed by the manufacturer. | 2 - 6 MPa (20 - 60 barg) |
| 207/A/FO | Main pilot 207/A/FOManual-setting main pilot for the Fail Open version; /D, /CS and /FIO remote-setting versions are listed by the manufacturer. | 4.1 - 7.4 MPa (41 - 74 barg) |
所列全部型号均可按您所需的认证、输出协议及过程连接方式供货 — 如需确定具体型号代码,请联系我们或提交询价。
本节目前仅提供英文版本

Gas transmission stations where supply continuity matters…

Power-generation fuel-gas supply and gas-reverse-flow…
Compression, booster, storage and regasification facilities

LNG marine transportation and gas liquefaction

Heavy industry with high gas demand
暂无评论
成为第一个评论此产品的人。
本节目前仅提供英文版本
Choose by the failure direction your station requires. The standard ASX 176 is Fail Close; the ASX 176/FO is Fail Open, and it needs at least 3 barg inlet pressure and a 2 barg differential. Overpressure protection must then be provided by a monitor or slam-shut. Confirm with your station designer.
204/A/FO: 0.1 to 3.3 MPa (1 to 33 barg); 205/A/FO: 2 to 6 MPa (20 to 60 barg); 207/A/FO: 4.1 to 7.4 MPa (41 to 74 barg). All are manual-setting; remote-setting versions /D, /CS and /FIO exist.
DN 25 (1 in), DN 50 (2 in), DN 80 (3 in), DN 100 (4 in) and DN 150 (6 in), with ASME B16.5 Class 300 or 600 flanges, RF or RTJ. Face-to-face lengths in Class 300 are 197, 267, 317, 368 and 473 mm; other connections on request to the manufacturer.
No price is published; it depends on the configuration and is given by quotation. The manufacturer states the product is certified to Directive 2014/68/EU (PED) and designed to EN 334; project-specific conformity documents can be requested with the inquiry. Attached: flyer FY0004ENG rev. B, technical brochure rev. A (24 pages) and the English User, Maintenance and Warning Manual rev. D.